FDM Basic Overview
Overview
Features and Functions
Features and Functions
Features and Functions
FDM Client ?C Basic Device Info (DD files)
FDM Client ?C Device Compare
FDM Client ?C Offline Configuration
Station Detail Display of HART Data
Station Detail Display of HART Data
EDDL and FDT-DTM
EDDL ?C Fisher DVC6000
DTM ?C Honeywell ST3000
Basic Architecture
Communications and HART Device Connections
Field Device Manager

FDM Basic Overview. Experion PKS

1. FDM Basic Overview

Experion PKS

2. Overview

FDM Field Device Manager
• Optimized for the field device maintenance
technician
• Connects to HART devices through Experion PKS
and non-Experion systems (MUXs and modems)
• User can view and modify HART device
configuration and setup information
• Supports large numbers of HART devices
• Supports vendor-tested Device Description (DD) and
EDDL files
• Supports FDT/DTM technology for HART devices
• Supports Profibus devices and HART over Profibus
via FDT/DTM only
• Based on open HCF SDC-625 and validated by the
HART vendor program
2
File Number- 2

3. Features and Functions

• Configuration of HART devices
- Online configuration and diagnostics of ANY HART device
from ANY vendor via DD/EDDL files or DTMs
- Optional off-line configuration of HART devices
Stored in FDM database
Downloaded to device when online
• HART device communications
- With Experion HART enabled IO
No extra wiring or hardware, communication via Ethernet, full
redundancy support
- With HART modems for bench configuration
Generic HART modem
DE HART Modem for MCToolkit
- With devices connected via hardware multiplexers
TPS/TDC/FSC/Safety Manager or any third party system
3
File Number- 3

4. Features and Functions

• Integration with Experion
- Auto build for devices connected to Experion HART IO
- Database changes made online
- Optional MUX Monitoring
Integration of diagnostic alarms from MUX-connected devices to
Experion
• Security
- All user access guarded by login and password
Flexible “role based security” environment
- Prevents changes during control to devices connected to
Experion PKS
- Application level security for devices connected to
multiplexers
4
File Number- 4

5. Features and Functions

• Instrument database functions
- Configuration History -- historical database records for all
device parameters
- Optional Audit Trail -- log of user actions with the device
parameter changes, diagnostics, calibration, etc.
Stored along with user name and reason for action
- Device documentation
Ability to store documents related to a device in the database
- Import / Export -- ability to import / export data to CSV,
Excel, HTML, XML formats
- Ability to backup current database and restore it later
• Integration with MC Toolkit
- Synchronize MC Toolkit data with FDM database
- Historize device testing and calibration results
5
File Number- 5

6. FDM Client ?C Basic Device Info (DD files)

FDM Client – Basic Device Info (DD files)
6
File Number- 6

7. FDM Client ?C Device Compare

FDM Client – Device Compare
7
File Number- 7

8. FDM Client ?C Offline Configuration

FDM Client – Offline Configuration
8
File Number- 8

9. Station Detail Display of HART Data

Normal HART
Detail Display Data
for Operations
9
FDM HART View
(DD or DTM) for
Maintenance
File Number- 9

10. Station Detail Display of HART Data

Device Alarms and
Alerts for
Maintenance
10
FDM Client
View for
Maintenance
File Number- 10

11. EDDL and FDT-DTM

• EDDL – Electronic Device Description Language
- Based on a text based programming language (DDL)
- Enhancements to DDL that is standardized across HART,
FF and Profibus
- IEC Standard IEC61804-2
• FDT-DTM – Field Device Technology – Device Type
Manager
- Based on Windows COM technology
- New Technology that Defines standards for “plug-in”
software applications (DTM’s) which exchange data with
the host application (FDT) across protocols
- IEC Standard IEC62453
11
File Number- 11

12. EDDL ?C Fisher DVC6000

EDDL – Fisher DVC6000
12
File Number- 12

13. DTM ?C Honeywell ST3000

DTM – Honeywell ST3000
13
File Number- 13

14. Basic Architecture

FDM Client
C
FDM Client
FDM Client
FDM Client
Experion
Experion
Station
Station
RCI
MODEM
Honeywell HART-DE Modem
B
RCI
Experion
Server
FDM
Server
Experion
Database
FDM/
Instrument
Database
(HART/Profibus)
A
RCI
FDM Client
PC
RCI
PC
RS232
RS232
RS232
RS485
MUX
RS485
MUX
MODEM
PMIO AI/AO
Series-A (1756) AI/AO
Series C I/O AI/AO
MUX
BASIC FDM
COMPONENTS
HART DEVICES
HART DEVICES
14
HART DEVICES
File Number- 14

15. Communications and HART Device Connections

HART device
Configuration
Database
RS-232
*HART
Modem
FDM
(Server)
HART
device
C
SW
MUX
*or HART-DE Modem
Ethernet / FTE
RS-232
A
Experion
Server
Experion
ERDB
RS-485
There are three
ways to connect
HART devices
ControlNet/FTE
CIOM-A (1756) AI/AO
B
Hardware MUX
MTL, P+F, R.Stahl,
Elcon, Arcom
HART
Protocol
Redundant PMIO AI/AO
Redundant Series C AI/AO
HART devices
HART devices
15
File Number- 15

16. Field Device Manager

Providing plant instrument engineers, technicians
and maintenance personnel with an optimized
environment that simplifies tasks and enables
remote management of smart instruments…
16
File Number- 16

17.

www.honeywell.com
English     Русский Правила