EPIMSB6
EPIB6
EPIMSB6&EPIB6
817.50K

EPIB6&EPIMSB6

1.

FWEC max, fanmotor output
Size
FWL,FWM,FWV
FWB
FWD
01
0.16 A
-
-
02
0.21 A
0.56 A
-
03
0.27 A
0.56 A
-
04
0.39 A
0.56 A
0.95 A
05
-
1.10 A
-
06
0.38 A
1.10 A
1.58 A
07
-
1.10 A
-
08
0.80 A
1.40 A
1.97 A
09
-
1.40 A
-
10
1.12 A
1.40 A
1.97 A
12
-
-
3.21 A
16
-
-
5.37 A
18
-
-
5.37 A
I = MAX. 3.2 A
No additional power
contactor needed !
+
I = MAX. 10 A !!

2.

Power contactor
FWV / FWL / FWM/ FWB /FWD
Remote Electronic
controller
Remote electronic
controller:
The EPIMSB6 power
interface is used for
connecting up to 4 units in
parallel to 1 controller.
Up to 4 units
EPIMSB6
The power interface is to
be installed on a DIN
guide, usually housed in
the electric boards cabinet.

3. EPIMSB6

Up to three EPIMSB6 can be connected to
the FWEC
EPIMSB6
Up to four fancoils (max current < 3,2 A
drawn per FCU unit) can be connected to
EPIMSB6. So up to twelve units can be
controlled by one controller
I < 3,2 A
EPIMSB6
EPIMSB6
Size
FWL,FWM,FWV
FWB
FWD
01
0.16 A
-
-
02
0.21 A
0.56 A
-
03
0.27 A
0.56 A
-
04
0.39 A
0.56 A
0.95 A
05
-
1.10 A
-
06
0.38 A
1.10 A
1.58 A
07
-
1.10 A
-
08
0.80 A
1.40 A
1.97 A
09
-
1.40 A
-
10
1.12 A
1.40 A
1.97 A
12
-
-
3.21 A
16
-
-
5.37 A
18
-
-
5.37 A

4. EPIB6

When current drawn by FCU > 3,2 A an
EPIB6 needs to be used. Only one FCU can
be connected on an EPIB6
EPIB6
I > 3,2A
Size
FWL,FWM,FWV
FWB
FWD
01
0.16 A
-
-
02
0.21 A
0.56 A
-
03
0.27 A
0.56 A
-
04
0.39 A
0.56 A
0.95 A
05
-
1.10 A
-
06
0.38 A
1.10 A
1.58 A
07
-
1.10 A
-
08
0.80 A
1.40 A
1.97 A
09
-
1.40 A
-
10
1.12 A
1.40 A
1.97 A
12
-
-
3.21 A
16
-
-
5.37 A
18
-
-
5.37 A

5. EPIMSB6&EPIB6

EPIMSB6&EPIB6
Solution when multiple fancoils with current >
3.2A needs to be connected to same control
EPIB6
I > 3.2A
EPIB6
I > 3.2A
EPIMSB6
EPIB6
I > 3.2A
EPIB6
I > 3.2A
English     Русский Правила